Methane Gas Detection Systems
Natural gas is mostly methane, so a methane gas detector is how commercial premises find a gas leak early. A fixed methane detection system monitors continuously, raises alarms at set levels and can shut off the gas automatically.
- Infrared or catalytic methane sensors
- Alarms at 10% and 20% of the lower explosive limit
- Linked to a gas solenoid valve for automatic shut-off
Quick answer
A methane gas detector measures natural gas in the air as a percentage of its lower explosive limit. Fixed commercial systems mount infrared or catalytic sensors near the ceiling, warn at about 10% LEL and shut off the gas through a solenoid valve at about 20% LEL, well before a flammable mixture can form.
- Sensor types
- Infrared, catalytic, semiconductor
- Alarm levels
- 10% and 20% LEL typical
- Mounting
- Within 300 mm of the ceiling
- Calibration
- At least annually
- How to book
- Call 020 8935 5572 or book online, 24/7
How methane gas detection works
A methane sensor measures the gas concentration in the air and reports it to a control panel as a percentage of the lower explosive limit (LEL). For methane, 100% LEL is about 4.4% gas in air. Alarms are set far below that, so action is taken long before a flammable mixture forms.
When the reading passes an alarm level, the panel switches relays that drive sounders and beacons, signal the building management system and, on high alarm, close the gas solenoid valve.
Methane sensor types
| Sensor | Strengths | Watch out for |
|---|---|---|
| Catalytic bead | Lower cost, proven, responds to most flammable gases | Needs oxygen; can be poisoned by silicones and some cleaning products |
| Infrared (NDIR) | Long life, fail-safe, not poisoned, works in low oxygen | Higher upfront cost |
| Semiconductor | Low cost, used in simple fixed alarms | More prone to drift and false alarms |
Where to fit a methane detector
- Methane is lighter than air: mount sensors within 300 mm of the ceiling
- Above the gas meter, governor and main isolation valve
- Above boiler burners and catering appliance connections
- In risers, ducts and voids that carry gas pipework
- Away from the direct airflow of extract grilles, which can dilute a leak
Methane leak detection versus a gas interlock
Methane detection responds to gas that has already escaped. A gas interlock stops gas being supplied when the ventilation is not running, and a gas proving system checks the pipework is sound before the gas opens. They solve different problems, and many commercial kitchens and plant rooms have more than one of them working through the same shut-off valve.
Calibration and sensor life
Every methane sensor should be calibrated at least annually with a certified test gas, and after any alarm or exposure to high concentrations. Catalytic sensors typically last three to five years; infrared sensors usually last longer. A calibration certificate is issued for each head.
Portable versus fixed methane detectors
Portable methane detectors and leak sniffers are used by engineers to find the exact source of a leak. They are not a substitute for a fixed methane detection system, which monitors around the clock and can isolate the gas without anyone present.
Frequently asked questions
How do you detect methane gas?
With a methane sensor. Fixed infrared or catalytic sensors monitor continuously and alarm at set levels; portable detectors are used by engineers to pinpoint a leak.
What is the best way to detect methane gas?
In commercial premises, a fixed methane detection system with infrared or catalytic sensors mounted at high level, linked to an automatic gas shut-off valve.
Is a methane detector the same as a natural gas detector?
Yes in practice. UK natural gas is mostly methane, so natural gas detectors use methane sensors.
What level should a methane alarm be set to?
Commonly a warning at 10% LEL and a high alarm with gas shut-off at 20% LEL, adjusted to the site's risk assessment.
Related guides
Natural Gas Detectors
Gas leak alarms for kitchens and plant rooms.
Gas Detection Systems
Fixed gas leak detection for commercial premises.
Boiler Room Gas Detection
Gas and CO detection with automatic boiler isolation.
Plant Room Gas Detection
Detection, isolation and ventilation in plant rooms.
Gas Solenoid Valves
Normally closed automatic shut-off valves.
Gas Interlock Systems
How kitchen gas is linked to the extract and supply fans.
Parts in stock — ready to fit
Held in UK stock and carried on our vans, so most jobs are fixed in one visit.
Replacement gas interlock systems
Complete panels & kits ready to fit
In stock today
Air pressure switches
Fan & gas proving pressure switches
In stock today
Gas solenoid valves
Normally closed safety shut-off valves
In stock today
Quick release gas catering hoses
Commercial ranges, bays & mobile catering
In stock today
Super universal thermocouples
Fits most commercial gas appliances
In stock today
Need a part fitted?
Same-day engineer dispatch with these parts on the van.
Gas Safe Registered
Commercial catering & plant
24/7 UK Response
Same-day emergency dispatch
Vetted Engineers
DBS checked for schools & care
Transparent Pricing
Fixed callout, quoted parts