Gas Safety Sensors & Controls

An interlock is only as reliable as the device proving ventilation. Choosing between a pressure switch, airflow sensor and current monitor is the single biggest factor in nuisance tripping.

  • Current monitoring proves the motor, not the airflow
  • Differential pressure is the most common proof of extract
  • Emergency stops must be on every escape route from the kitchen

System architecture

Fan SensorsPressure / airflow / currentEmergency StopLatching e-stop buttonsGas DetectionMethane · CO · CO₂Interlock ControllerGas safety control panelProving PanelPressure proving testSolenoid ValveNormally closed shut-offAppliancesCatering / boilersproving result
Interlock Controller → Fan Sensors → Proving Panel → Solenoid Valve. Losing any proof of ventilation de-energises the valve and isolates the gas supply.

Sensing device comparison

DeviceProvesStrengthsWatch out for
Differential air pressure switchPressure drop across fan or filterCheap, widely used, adjustableDrifts with filter loading; nuisance trips if set too tight
Duct airflow / velocity sensorActual air movement in the ductTrue airflow proof, good for variable speedNeeds clean straight duct run and grease protection
Fan current monitoring sensorMotor is drawing running currentSimple, unaffected by greaseA spinning fan with a slipping belt still passes
Fan speed / VSD statusDrive is running at set speedIntegrates with BMSDrive status is not proof of air delivery

Emergency gas shut-off buttons

  • Latching mushroom head or key-reset, clearly labelled GAS
  • Sited on each exit route, typically 1.2–1.4m above floor
  • Wired to de-energise the solenoid valve directly through the panel
  • Functionally tested at every annual service

Set-up and calibration

Sensing devices are commissioned with the kitchen at full load and clean filters, then the set point is backed off to a repeatable margin. Record the measured value, the set point and the trip time on the commissioning certificate.

Frequently asked questions

Which sensor causes the fewest nuisance trips?

A correctly commissioned airflow sensor or a current monitor combined with a pressure switch. A single tightly set pressure switch is the most common nuisance-trip cause.

How many emergency stops does a kitchen need?

Enough that a person can isolate gas on any escape route without passing the appliances — usually one per exit.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Merlin, Medem, Intelligas, S&S Northern

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today

  • Need a part fitted?

    Same-day engineer dispatch with these parts on the van.

  • Gas Safe Registered

    Commercial catering & plant

  • 24/7 UK Response

    Same-day emergency dispatch

  • Vetted Engineers

    DBS checked for schools & care

  • Transparent Pricing

    Fixed callout, quoted parts

Call UsWhatsApp