Fault guide

Gas Interlock Won't Reset

A gas interlock that will not reset is doing its job: it is holding the gas closed because one of its safety inputs is not satisfied. The reset button only latches once the panel sees mains power, a healthy emergency stop circuit, proven ventilation and (on proving systems) a sound pipework test.

  • Most no-reset calls are an unlatched e-stop, a fan not running, or a pressure switch out of adjustment
  • Never bypass, strap out or wedge an interlock input to get the kitchen cooking
  • Same-day UK attendance to diagnose, repair and recertify

System architecture

Fan SensorsPressure / airflow / currentEmergency StopLatching e-stop buttonsGas DetectionMethane · CO · CO₂Interlock ControllerGas safety control panelProving PanelPressure proving testSolenoid ValveNormally closed shut-offAppliancesCatering / boilersproving result
Interlock Controller → Fan Sensors → Proving Panel → Solenoid Valve. Losing any proof of ventilation de-energises the valve and isolates the gas supply.

Reset sequence — how it should work

  • Extract fan (and make-up air fan where fitted) switched on at the panel or BMS
  • Fan runs up and the air pressure switch or airflow sensor makes, proving ventilation
  • All emergency stop buttons are out and latched in the healthy position
  • Gas detection heads, where fitted, are in a clear, non-alarm state
  • Press and hold reset — the panel energises the solenoid valve coil and the gas-on lamp lights

Why it won't latch

Symptom at the panelLikely causeWhat is needed
Emergency stop lamp litA button pressed in somewhere in the kitchen or plant roomFind and twist-release every e-stop, including ones behind equipment
Fan fail lamp litFan not running, belt slipping, isolator off, or pressure switch not makingFan and airflow proving fault diagnosis
No lamps at allBlown fuse, tripped supply, dead transformer or failed panelElectrical supply test and panel repair or replacement
Resets then drops out seconds laterMarginal airflow proof, dirty filters, intermittent switch or loose terminalPressure switch setting and airflow measurement
Panel resets but no gas at appliancesSolenoid coil open circuit, valve stuck shut, or manual valve closedSolenoid valve test and replacement
Proving lockout codePipework failed the pressure proof — possible leak or open appliance tapTightness test before any reset

Safe checks a kitchen manager can make

  • Check every emergency stop button is fully released
  • Confirm the extract canopy fan is actually pulling air, not just switched on at the panel
  • Check all appliance isolation taps are closed before attempting a reset on a proving system
  • Check the kitchen ventilation isolator and the panel's fused supply have not been switched off by cleaners
  • Record the exact lamps and codes showing — it speeds up the call-out

If you can smell gas

  • Turn off the gas at the emergency control valve and press the emergency stop button
  • Do not switch anything electrical on or off, and do not use naked flames
  • Open doors and windows, evacuate and keep people clear
  • Call the National Gas Emergency Service on 0800 111 999
  • Only then call us to make the installation safe and return it to service

Frequently asked questions

Can I bypass the interlock to keep cooking?

No. Bypassing the interlock removes the ventilation safety and makes the installation immediately dangerous and non-compliant with BS 6173. An engineer must find and fix the fault.

Why does the interlock reset then trip again?

That usually means ventilation is only marginally proven — a pressure switch set too close to the actual duct pressure, blocked filters, a slipping fan belt, or a loose terminal breaking the safety circuit intermittently.

How quickly can you attend?

We run a 24/7 UK response desk and carry replacement panels, air pressure switches and solenoid valves in stock, so most no-reset faults are repaired on the first visit.

Will I get paperwork afterwards?

Yes. Every repair is followed by a full interlock test — fan fail, emergency stop and valve closure — and a certificate for your compliance file.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Merlin, Medem, Intelligas, S&S Northern

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today

  • Need a part fitted?

    Same-day engineer dispatch with these parts on the van.

  • Gas Safe Registered

    Commercial catering & plant

  • 24/7 UK Response

    Same-day emergency dispatch

  • Vetted Engineers

    DBS checked for schools & care

  • Transparent Pricing

    Fixed callout, quoted parts

Call UsWhatsApp