Answer library · A–Z

Gas interlock questions answered

Every answer below responds to a question people in the UK actually search for. Each one is short enough to read in seconds and links to the full guide.

  • Answers to real UK searches
  • Short, direct answers first
  • Links to the full guide for each topic

Quick answer

A gas interlock system only lets gas reach commercial kitchen appliances while the ventilation fans are proven running. Gas solenoid valves do the shutting off, air pressure switches prove the airflow, gas proving checks the pipework is tight, and a CP42 certificate records that the whole installation has been tested.

Questions
30 answered
Standards
BS 6173, IGEM/UP/19, IGEM/UP/11
How to book
Call 020 8935 5572 or book online, 24/7

How to use this library

Questions are listed alphabetically. Each answer is written to stand on its own, so you can share a single answer with a colleague, landlord or insurer.

If your question is about a fault happening now, use the Interlock Fault Finder or call an engineer: do not bypass an interlock or solenoid valve to keep cooking.

Do I need a gas interlock system?

Yes, in almost every commercial kitchen with mechanical extraction. BS 6173 requires gas supply to catering appliances to be interlocked with the ventilation system, and a Gas Safe engineer will normally record a missing interlock as a defect on a CP42 inspection.

Do you need a gas proving system for a boiler room?

It is recommended where a shut-off valve can close automatically, because proving checks no burner valve or joint is open before the gas is restored.

Do you need a gas safety certificate for commercial properties?

Commercial catering premises are expected to have their gas installation inspected and certified by a Gas Safe engineer, normally every 12 months. The CP42 record is what insurers, landlords and environmental health officers ask to see.

How do you detect methane gas?

With a methane sensor. Fixed infrared or catalytic sensors monitor continuously and alarm at set levels; portable detectors are used by engineers to pinpoint a leak.

How do you install a gas interlock system?

Survey the gas and ventilation, size and fit the solenoid valve on the kitchen supply, fit airflow sensors to each fan, mount the panel and E-stops, wire everything, then tightness-test and commission by proving the gas shuts off on fan failure.

How do you reset a gas solenoid valve?

Most kitchen valves reset automatically when the interlock or proving panel restores power. Manual reset valves have a lever or knob that is lifted to latch the valve open once the fault is cleared. If it will not stay open, the cause must be found rather than forced.

How do you test a gas solenoid valve?

A Gas Safe engineer checks the coil voltage and resistance, confirms the valve opens and closes on command from the panel, and carries out a let-by and tightness test to prove the valve seals fully when closed.

How do you test an air pressure switch?

With the fans running, the engineer measures the duct pressure with a manometer, checks the switch changes state at its set point, then stops the fan to confirm the switch opens and the interlock closes the gas.

How does a gas interlock system work?

Air pressure switches or current sensors prove the ventilation fans are running. The interlock panel then opens a normally-closed gas solenoid valve. If a fan stops, a sensor fails or the emergency stop is pressed, the panel removes power from the valve and the gas closes.

How does a gas proving system work?

On start-up the panel opens a small bypass or pump to raise pressure in the pipework, then monitors a pressure switch for a set time. If pressure holds, the main solenoid opens. If it falls, the panel locks out and shows a fault.

How does a gas solenoid valve work?

When voltage reaches the coil, a magnetic field lifts the plunger off its seat and gas flows. When the voltage is removed, a spring returns the plunger and seals the valve. Most kitchen valves are normally-closed and 230V AC.

How does an air pressure switch work in a kitchen interlock?

The switch is piped to the extract duct and measures the pressure difference created by the fan. When the fan is running and the difference exceeds the set point, the contacts close and tell the interlock panel airflow is proven.

How much is a commercial gas safety certificate?

The price depends on the number of appliances, whether an interlock and gas detection are fitted, and access. We give a fixed price after a short call about the kitchen, before any visit is booked.

How often should a gas interlock be serviced?

At least once a year, and after any change to the ventilation or gas installation. Many kitchens combine it with their annual CP42 gas safety inspection.

Is a catering gas certificate the same as a CP42?

Yes. Catering gas certificate, commercial kitchen gas safety certificate and CP42 all describe the same annual commercial catering gas inspection record.

Is a gas interlock system a legal requirement?

The Gas Safety (Installation and Use) Regulations require gas installations to be safe; BS 6173 is the recognised standard that sets out how, and it requires a ventilation interlock where mechanical extraction is installed. Insurers and environmental health officers enforce it in practice.

What are the requirements for boiler room gas detection?

There is no blanket legal requirement, but the installation must be safe. Detection with automatic gas shut-off is normally specified where the boiler room is confined, below ground, rarely occupied or mechanically ventilated, and insurers often require it.

What is a CP42 certificate?

A CP42 is the gas safety record for commercial catering premises. A Gas Safe engineer with catering qualifications issues it after inspecting and testing the kitchen gas pipework, appliances, ventilation and interlock.

What is a gas interlock system?

A gas interlock system is a safety control that only allows gas to flow to commercial kitchen appliances while the extract and supply ventilation fans are proven to be running. If airflow fails, a solenoid valve closes and shuts off the gas automatically.

What is a gas proving system?

A gas proving system checks the downstream pipework is gas-tight before opening the main valve. It pressurises the pipework briefly and watches for pressure loss; if appliance taps are left open or there is a leak, the gas will not turn on.

What is a gas proving unit?

A gas proving unit is the control panel and valves that test the gas pipework for leaks or open appliance taps before the main gas solenoid valve is allowed to open. It is also called a gas proving panel or gas pressure proving system.

What is a gas solenoid valve?

A gas solenoid valve is an electrically operated shut-off valve. It stays closed with no power and opens only when the interlock or proving panel energises its coil, so any loss of power or safety signal closes the gas supply.

What is a low gas pressure switch?

A switch that opens when the gas supply pressure falls below its set point, so the burner or proving panel locks out instead of running on too little gas.

What is an automatic gas shut off valve for a commercial kitchen?

A normally closed solenoid valve that only stays open while the interlock panel powers it. Any fault, alarm, emergency stop or power cut removes the power and the valve shuts the gas.

What is boiler room gas detection?

A fixed system of methane and carbon monoxide sensors wired to a control panel that warns of a gas leak or poor combustion in a boiler room and closes a gas solenoid valve on high alarm, even when nobody is there.

What is cellar room gas detection?

A fixed system of gas sensors and a control panel that monitors a cellar for carbon dioxide from drinks dispense, and natural gas or carbon monoxide where a meter or boiler is present, warning staff at the cellar door before they enter.

What types of gas solenoid valve are there?

Normally closed valves, which shut when power is lost and are used for safety shut-off; normally open valves, which close when energised; and manual reset valves, which must be latched open by hand after a trip. They come in threaded sizes from 15mm to 2 inch and flanged sizes for larger supplies.

Where should a CO₂ detector be placed in a cellar?

Low down, within about 300 mm of the floor, near the gas cylinders, bulk tank and dispense equipment, because carbon dioxide is heavier than air and collects at floor level.

Where should the emergency gas shut off button be in a commercial kitchen?

On the escape routes out of the kitchen, clearly labelled and easy to reach, so staff can shut off the gas on their way out without passing the cooking line.

Why does my gas interlock keep tripping?

Usually because airflow is not being proven consistently: a dirty filter or blocked sensor tube, a pressure switch set too close to the fan's running pressure, a slipping fan belt, or a loose connection. Repeated tripping should be investigated rather than bypassed.

Frequently asked questions

Do I need a gas interlock system?

Yes, in almost every commercial kitchen with mechanical extraction. BS 6173 requires gas supply to catering appliances to be interlocked with the ventilation system, and a Gas Safe engineer will normally record a missing interlock as a defect on a CP42 inspection.

Do you need a gas proving system for a boiler room?

It is recommended where a shut-off valve can close automatically, because proving checks no burner valve or joint is open before the gas is restored.

Do you need a gas safety certificate for commercial properties?

Commercial catering premises are expected to have their gas installation inspected and certified by a Gas Safe engineer, normally every 12 months. The CP42 record is what insurers, landlords and environmental health officers ask to see.

How do you detect methane gas?

With a methane sensor. Fixed infrared or catalytic sensors monitor continuously and alarm at set levels; portable detectors are used by engineers to pinpoint a leak.

How do you install a gas interlock system?

Survey the gas and ventilation, size and fit the solenoid valve on the kitchen supply, fit airflow sensors to each fan, mount the panel and E-stops, wire everything, then tightness-test and commission by proving the gas shuts off on fan failure.

How do you reset a gas solenoid valve?

Most kitchen valves reset automatically when the interlock or proving panel restores power. Manual reset valves have a lever or knob that is lifted to latch the valve open once the fault is cleared. If it will not stay open, the cause must be found rather than forced.

How do you test a gas solenoid valve?

A Gas Safe engineer checks the coil voltage and resistance, confirms the valve opens and closes on command from the panel, and carries out a let-by and tightness test to prove the valve seals fully when closed.

How do you test an air pressure switch?

With the fans running, the engineer measures the duct pressure with a manometer, checks the switch changes state at its set point, then stops the fan to confirm the switch opens and the interlock closes the gas.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Complete panels & kits ready to fit

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today