Technical guide

Gas Interlock Wiring Diagram Explained

Every interlock follows the same logic regardless of make: the controller only energises the gas solenoid valve when the emergency stop circuit is healthy and the ventilation proving contact is made.

  • Understand the circuit before you troubleshoot a tripping interlock
  • Terminal notes for the common interlock panel types
  • Wiring alterations must be carried out by a competent electrical and Gas Safe engineer

Quick answer

A gas interlock wiring diagram shows the panel's mains supply, the airflow sensor inputs for each fan, the emergency stop loop, the gas solenoid valve output and any fan-start, fire alarm or gas detection links. Wiring must be carried out and tested by a competent, Gas Safe registered engineer.

Inputs
Airflow sensors, E-stops, fire alarm, detection
Output
Normally-closed gas solenoid valve
Standards
BS 6173, IGEM/UP/19, IGEM/UP/11

System architecture

Fan SensorsPressure / airflow / currentEmergency StopLatching e-stop buttonsGas DetectionMethane · CO · CO₂Interlock ControllerGas safety control panelProving PanelPressure proving testSolenoid ValveNormally closed shut-offAppliancesCatering / boilersproving result
Interlock Controller → Fan Sensors → Proving Panel → Solenoid Valve. Losing any proof of ventilation de-energises the valve and isolates the gas supply.

The standard circuit

  • 230V supply into the controller through a dedicated fused, labelled isolator
  • Emergency stop wired as a normally closed series loop — break it and the valve drops out immediately
  • Air proving device (differential pressure switch, airflow sensor or fan current monitor) into the proving input as a volt-free contact
  • Volt-free run/enable output to the ventilation panel or fan starter where the interlock also starts the fans
  • Switched live to the gas solenoid valve coil — normally closed, so loss of signal closes the gas
  • Optional gas detection or CO/CO₂ alarm input that also drops the valve

Wiring notes by panel type

Panel typeWiring notes
Current sensing interlock panelsSeparate terminal blocks for e-stop loop, air proving and valve output; valve output is switched live and must not be shared with fan control
Air pressure switch panelsAir pressure switch across the extract; e-stop in series with the proving line; verify the valve coil voltage (230V) before connecting
Gas proving panelsProving input expects a volt-free contact — do not feed a live signal into it

Common wiring mistakes we find

  • Emergency stop wired normally open, so pressing it does nothing
  • Air pressure switch piped the wrong way round, so it proves with the fan off
  • Valve coil fed from the fan supply rather than the interlock output, defeating the interlock entirely
  • Proving input bridged out during a fault and never reinstated — a serious defect

How the work is carried out

Every job starts with a proper look at the site rather than a guess over the phone. The engineer confirms the gas supply size and pressure, the appliances on the line, the ventilation arrangement and the position of the existing or proposed control panel. From that survey the correct solenoid valve size, proving devices and panel are selected, and you get a fixed written quotation before any work begins.

On the day, the gas supply is isolated and the work is carried out by a Gas Safe registered engineer holding the relevant commercial catering qualifications. Pipework alterations are made to current standards, the interlock wiring is installed and labelled, and the whole system is then commissioned: the fans are started, the proving is checked, the emergency stops are tested, and the gas is only released once every safety function works exactly as it should.

You are left with a working system, a demonstration for your staff, and the paperwork — a commissioning record and test certificate that go straight into your gas safety file for insurers, landlords and environmental health.

Parts and equipment we use

We fit proven commercial-grade equipment rather than the cheapest available parts, because an interlock that nuisance-trips or fails early costs a kitchen far more in lost trading than it saves on the invoice. Panels from the established UK manufacturers are all supplied, wired and commissioned by our engineers.

Solenoid valves are normally closed, power-to-open safety shut-off valves sized to the pipework, from 22mm and 28mm on smaller lines up to flanged valves on large range supplies. Airflow proving is matched to the ventilation: differential air pressure switches across the fans, or current sensors where pressure tapping is impractical.

The common failure items — replacement interlock panels, gas solenoid valves, air pressure switches, quick-release catering hoses and universal thermocouples — are carried in stock on the van, which is why most repairs and replacements are completed in a single visit.

Areas we cover

Our engineers cover the whole of London, Surrey and the M25 corridor, including the City and West End, the inner and outer London boroughs, Kingston, Epsom, Guildford, Woking and the Surrey towns, and the Home Counties belt through Watford, St Albans, Slough, Sevenoaks and the Dartford crossing area.

Planned work is booked to suit your trading hours — early mornings, evenings, nights and weekends are all available for kitchens that cannot close during service. Emergency call-outs for kitchens with no gas are attended the same day wherever possible, and out-of-hours access, permits and risk assessments are handled for managed sites and shopping centres.

Frequently asked questions

How does a gas interlock system work?

Air pressure switches or current sensors prove the ventilation fans are running. The interlock panel then opens a normally-closed gas solenoid valve. If a fan stops, a sensor fails or the emergency stop is pressed, the panel removes power from the valve and the gas closes.

Can you send me a wiring diagram for my panel?

Tell us the make and model and we will point you to the manufacturer's current diagram. We do not publish altered copies, because terminal numbering changes between revisions.

Is bridging out the proving input ever acceptable?

No. Bridging the ventilation proving signal removes the safety function and would fail any inspection. If the kitchen must trade, the gas stays isolated until the fault is fixed.

Does the interlock have to start the fans?

Not necessarily, but it is the usual arrangement in commercial kitchens: one switch starts ventilation and only then releases the gas.

Are your engineers Gas Safe registered for commercial catering?

Yes. All gas work is carried out by Gas Safe registered engineers holding the commercial catering categories needed for kitchen appliances, pipework and interlock systems. Registration details are available on request and shown on the engineer's ID card on site.

Can you work outside our opening hours?

Yes. Most of our commercial kitchen work is planned around service — early mornings, evenings, overnight and weekends — so the kitchen stays open when it needs to be. Out-of-hours working is quoted as part of the job, not as a surprise extra.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Complete panels & kits ready to fit

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today

  • Need a part fitted?

    Same-day engineer dispatch with these parts on the van.

  • Gas Safe Registered

    Commercial catering & plant

  • 24/7 UK Response

    Same-day emergency dispatch

  • Vetted Engineers

    DBS checked for schools & care

  • Transparent Pricing

    Fixed callout, quoted parts

Call Us