Air Pressure Switch Repair & Replacement

The differential air pressure switch is the part that proves the kitchen extract is moving air. It is also the most common failure point on a gas interlock — a £30 switch that stops a whole kitchen cooking when it drifts or blocks.

  • Fan and gas proving air pressure switches in stock today
  • Set to a measured duct pressure, not wound down until the fault clears
  • Interlock retested and certified after every switch change

How it works

The switch senses the pressure difference across the extract fan or a duct tapping through two small sensing tubes. When the fan runs and the differential exceeds the set point, the switch contacts make and the interlock panel accepts ventilation as proven, energising the gas solenoid valve. Lose the differential and the contacts break and the gas closes.

Common faults

FaultSymptomRepair
Set point too highGas drops out with the fan running normallyMeasure and reset within range
Sensing tubes blocked or greasyRandom fan faults, worse after cleaning is skippedClean or replace tubing and tappings
Tubes on the wrong portsNever proves, or proves with the fan offRefit high and low correctly
Perished diaphragmSticky, slow or dead switchingReplace the switch
Corroded or loose terminalsIntermittent trips mid-serviceRe-terminate and test
Wrong switch range for the ductCannot be set reliably at allFit a switch with the correct pressure range

What a proper repair includes

  • Measured differential pressure across the fan at operating condition
  • Set point documented, with a sensible margin above proven airflow
  • Sensing tubes renewed and routed so grease and condensate cannot collect
  • Full interlock function test: fan fail, emergency stop and valve closure
  • Certificate for the compliance file

If you can smell gas

  • Turn off the gas at the emergency control valve and press the emergency stop button
  • Do not switch anything electrical on or off, and do not use naked flames
  • Open doors and windows, evacuate and keep people clear
  • Call the National Gas Emergency Service on 0800 111 999
  • Only then call us to make the installation safe and return it to service

Frequently asked questions

Can I adjust the pressure switch myself?

It should be set against a measured duct pressure by a competent engineer. Adjusting it by trial and error can leave the system proving ventilation that is not actually there.

How long do air pressure switches last?

Typically five to ten years in a kitchen environment, but grease, heat and dirty filters shorten that considerably. They are checked at every annual interlock service.

Do you carry them in stock?

Yes — fan proving and gas proving air pressure switches are stock items, fitted same day in most cases.

Is a current monitor better?

A fan current monitor proves the motor is loaded but not that air is moving; a differential pressure switch or airflow sensor is the stronger proof and is what we normally recommend.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Merlin, Medem, Intelligas, S&S Northern

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today

  • Need a part fitted?

    Same-day engineer dispatch with these parts on the van.

  • Gas Safe Registered

    Commercial catering & plant

  • 24/7 UK Response

    Same-day emergency dispatch

  • Vetted Engineers

    DBS checked for schools & care

  • Transparent Pricing

    Fixed callout, quoted parts

Call UsWhatsApp