Answer hub · Faults
Gas interlock faults and symptoms
Match what you see in the kitchen to the most likely cause, then follow the safe next step. Never bypass an interlock to keep cooking.
- Symptom-to-cause table
- Safe first checks
- Links to each fault guide
Quick answer
Most gas interlock faults are airflow problems: a fan stopped or running slowly, a blocked sensor tube or a failed air pressure switch. Others are a tripped emergency stop, a failed gas solenoid valve coil, or a gas proving lockout caused by an open appliance tap or leak.
- First checks
- Fans running, E-stops released, taps closed
- Never
- Bypass the interlock or valve
- Response
- Same-day emergency call-outs
Symptoms and likely causes
| Symptom | Likely cause | Guide |
|---|---|---|
| No gas, panel shows fan fault | Fan stopped, belt slipping, air pressure switch failed | Fan fault / pressure switch |
| Panel won't reset | Emergency stop pressed, airflow not proven, proving lockout | Interlock won't reset |
| Gas cuts out when extraction starts | Pressure switch set too close to running pressure, unbalanced supply/extract | Gas trips with extraction |
| Solenoid valve hums or is hot | Coil failing, wrong voltage, debris on seat | Solenoid valve fault |
| Proving fails at start-up | Appliance tap open, leaking joint or valve | Proving system fault |
| Gas trips during service | Filter blocked, sensor tube split, loose connection | Fault diagnosis |
Safe first checks
- Check extract and supply fans are running
- Release any emergency stop buttons
- Make sure every appliance tap is fully closed
- Try one reset only; if it fails again, call an engineer
- If you smell gas, leave, isolate the supply and call the gas emergency number 0800 111 999
Frequently asked questions
Why does my gas interlock keep tripping?
Usually because airflow is not being proven consistently: a dirty filter or blocked sensor tube, a pressure switch set too close to the fan's running pressure, a slipping fan belt, or a loose connection.
Can I bypass the interlock to keep cooking?
No. Bypassing a gas interlock removes the safety shut-off and is dangerous and non-compliant. Call an engineer; most faults are fixed on the first visit.
Related guides
Interlock Fault Diagnosis
Step-by-step diagnosis of interlock trips.
Interlock Won't Reset
Why a panel refuses to reset.
Air Pressure Switch Repair
Testing and replacing airflow switches.
Interlock Repair
Fault-finding and same-day parts from van stock.
Interlock Fault Finder
Diagnose a trip in three questions.
Gas Solenoid Valves
Normally-closed shut-off valves explained.
Parts in stock — ready to fit
Held in UK stock and carried on our vans, so most jobs are fixed in one visit.
Replacement gas interlock systems
Complete panels & kits ready to fit
In stock today
Air pressure switches
Fan & gas proving pressure switches
In stock today
Gas solenoid valves
Normally closed safety shut-off valves
In stock today
Quick release gas catering hoses
Commercial ranges, bays & mobile catering
In stock today
Super universal thermocouples
Fits most commercial gas appliances
In stock today
Need a part fitted?
Same-day engineer dispatch with these parts on the van.
Gas Safe Registered
Commercial catering & plant
24/7 UK Response
Same-day emergency dispatch
Vetted Engineers
DBS checked for schools & care
Transparent Pricing
Fixed callout, quoted parts