Quick answer

Most gas interlock faults are airflow problems: a fan stopped or running slowly, a blocked sensor tube or a failed air pressure switch. Others are a tripped emergency stop, a failed gas solenoid valve coil, or a gas proving lockout caused by an open appliance tap or leak.

First checks
Fans running, E-stops released, taps closed
Never
Bypass the interlock or valve
Response
Same-day emergency call-outs

Symptoms and likely causes

SymptomLikely causeGuide
No gas, panel shows fan faultFan stopped, belt slipping, air pressure switch failedFan fault / pressure switch
Panel won't resetEmergency stop pressed, airflow not proven, proving lockoutInterlock won't reset
Gas cuts out when extraction startsPressure switch set too close to running pressure, unbalanced supply/extractGas trips with extraction
Solenoid valve hums or is hotCoil failing, wrong voltage, debris on seatSolenoid valve fault
Proving fails at start-upAppliance tap open, leaking joint or valveProving system fault
Gas trips during serviceFilter blocked, sensor tube split, loose connectionFault diagnosis

Safe first checks

  • Check extract and supply fans are running
  • Release any emergency stop buttons
  • Make sure every appliance tap is fully closed
  • Try one reset only; if it fails again, call an engineer
  • If you smell gas, leave, isolate the supply and call the gas emergency number 0800 111 999

Frequently asked questions

Why does my gas interlock keep tripping?

Usually because airflow is not being proven consistently: a dirty filter or blocked sensor tube, a pressure switch set too close to the fan's running pressure, a slipping fan belt, or a loose connection.

Can I bypass the interlock to keep cooking?

No. Bypassing a gas interlock removes the safety shut-off and is dangerous and non-compliant. Call an engineer; most faults are fixed on the first visit.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Complete panels & kits ready to fit

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today

  • Need a part fitted?

    Same-day engineer dispatch with these parts on the van.

  • Gas Safe Registered

    Commercial catering & plant

  • 24/7 UK Response

    Same-day emergency dispatch

  • Vetted Engineers

    DBS checked for schools & care

  • Transparent Pricing

    Fixed callout, quoted parts

Call Us