Gas interlock system type

Demand-Controlled Ventilation Gas Interlock

Where kitchen fans run at variable speed to save energy, the interlock must still prove adequate ventilation at every speed. These systems combine fan-speed control with CO₂ monitoring and proving so gas is isolated if ventilation is inadequate.

  • Energy savings
  • CO₂ monitoring
  • Minimum-speed proving

Quick answer

Where kitchen fans run at variable speed to save energy, the interlock must still prove adequate ventilation at every speed. These systems combine fan-speed control with CO₂ monitoring and proving so gas is isolated if ventilation is inadequate.

Standards
BS 6173, IGEM/UP/19, IGEM/UP/11
In stock
Interlock panels, gas solenoid valves, air pressure switches
How to book
Call 020 8935 5572 or book online, 24/7

System architecture

Fan SensorsPressure / airflow / currentEmergency StopLatching e-stop buttonsGas DetectionMethane · CO · CO₂Interlock ControllerGas safety control panelProving PanelPressure proving testSolenoid ValveNormally closed shut-offAppliancesCatering / boilersproving result
Interlock Controller → Fan Sensors → Proving Panel → Solenoid Valve. Losing any proof of ventilation de-energises the valve and isolates the gas supply.

What is a demand-controlled ventilation gas interlock?

Where kitchen fans run at variable speed to save energy, the interlock must still prove adequate ventilation at every speed. These systems combine fan-speed control with CO₂ monitoring and proving so gas is isolated if ventilation is inadequate.

How it works

  • Fans modulate based on cooking load or sensors.
  • Proving is set for the minimum safe speed.
  • CO₂ monitoring confirms air quality.
  • Inadequate ventilation isolates the gas.

Best suited to

  • Energy-saving kitchen retrofits
  • Large, variable-use kitchens
  • Sites with inverter fans

Key features

  • Energy savings
  • CO₂ monitoring
  • Minimum-speed proving
  • Integrated controls

What we test at commissioning and service

  • Proving at minimum speed
  • CO₂ thresholds
  • Shut-off confirmed
  • Speed control reviewed

Supplied, installed and commissioned

Every demand-controlled ventilation gas interlock we fit is installed by Gas Safe registered commercial catering engineers and commissioned to BS 6173 and IGEM/UP/19. Commissioning includes failing each fan in turn, testing the emergency stop, confirming the gas solenoid valve closes, and recording the results.

You receive a written commissioning record, and the system can be included in your annual CP42 commercial gas safety certificate inspection.

Parts carried in stock

  • Replacement gas interlock systems
  • Gas solenoid valves in common sizes
  • Air pressure switches
  • Quick release gas catering hoses
  • Super universal thermocouples

Repair, servicing and replacement

If your system stops resetting, keeps tripping or the gas will not come on, our engineers diagnose the fault on site. Most faults are a fan proving problem, a failed valve coil, an open emergency stop circuit or wiring disturbed during other work.

Annual servicing tests every safety function and is usually combined with the CP42 inspection to minimise disruption.

Regulations

BS 6173 requires gas supplies to commercial catering appliances to be interlocked with mechanical ventilation so appliances cannot operate without it. IGEM/UP/19 covers the design and application of interlock devices and CO₂ monitoring. The Gas Safety (Installation and Use) Regulations 1998 require installations to be maintained in a safe condition.

Compare gas interlock system types

TypeSummary
Current Sensing Gas InterlockProves supply and extract fans by monitoring the electrical current they draw.
Air Pressure Switch Gas InterlockUses differential air pressure switches on the ductwork to prove the fans are moving air.
Airflow Sensing Gas InterlockDirectly proves air flowing through the ventilation system with an airflow sensor.
2-Fan Gas InterlockMonitors one supply (make-up air) fan and one extract fan — the most common kitchen set-up.
4-Fan / Multi-Fan Gas InterlockFor larger kitchens with several supply and extract fans or multiple canopies.
Gas Interlock with Gas Pressure ProvingVentilation interlock plus a downstream gas tightness check before gas is allowed on.
Gas Interlock with CO₂ MonitoringMonitors kitchen CO₂ and can isolate gas when levels reach set limits.
Gas Interlock with CO / Gas DetectionAdds carbon monoxide, natural gas (methane) or LPG detection to the interlock.
Gas Interlock with Fire Alarm InterfaceIsolates the kitchen gas automatically when the building fire alarm activates.
Gas Interlock with BMS InterfaceSends status and fault signals from the interlock to a building management system.
Demand-Controlled Ventilation Gas InterlockIntegrates gas safety with variable fan speed and demand-controlled ventilation.
Intelligent / Digital Gas InterlockDisplay-based panels with diagnostics, configurable inputs, alarms and event logs.
Boiler Room Gas Interlock & Proving SystemDesigned around plant-room and boiler-house gas safety rather than catering.
Laboratory Gas Interlock & Proving SystemGas proving and interlocking for school and college laboratory gas services.

From our engineers' vans

Photos from real jobs — the equipment described on this page, installed and serviced by our engineers.

GI-100 gas interlock panel — front, side, bottom and installed views with power, supply, extract, gas on and fault indicators
GI-100 gas interlock panel — 180 × 130 × 60 mm, key reset & emergency stop
Kitchen safety interlock panel installed by our engineers
Kitchen gas interlock panel — installed and commissioned
Boiler plant controller checked during a plant room visit
Plant room controls checked during gas safety visit

Frequently asked questions

Is demand-controlled ventilation safe with gas?

Yes, when the interlock proves ventilation at all speeds and CO₂ is monitored, in line with IGEM/UP/19 guidance.

Will it save energy?

Running fans slower during quiet periods can reduce energy use significantly; savings depend on your usage.

Related guides

Parts in stock — ready to fit

Held in UK stock and carried on our vans, so most jobs are fixed in one visit.

  • Replacement gas interlock systems

    Complete panels & kits ready to fit

    In stock today

  • Air pressure switches

    Fan & gas proving pressure switches

    In stock today

  • Gas solenoid valves

    Normally closed safety shut-off valves

    In stock today

  • Quick release gas catering hoses

    Commercial ranges, bays & mobile catering

    In stock today

  • Super universal thermocouples

    Fits most commercial gas appliances

    In stock today

  • Need a part fitted?

    Same-day engineer dispatch with these parts on the van.

  • Gas Safe Registered

    Commercial catering & plant

  • 24/7 UK Response

    Same-day emergency dispatch

  • Vetted Engineers

    DBS checked for schools & care

  • Transparent Pricing

    Fixed callout, quoted parts

Call Us